Chapter 2. Configuring
PELLERIN MILNOR CORPORATION
2.1.2.
Configuration decisions
2.1.2.1.
Selecting the Formula Set
—DIP switch position 1 determines the formula set used. Set
this switch position
on
(press the side nearest the number down) to configure the machine for the
four primary formulas. Set this switch
off
(press the side nearest the word “OFF” down) to use the
secondary set of formulas. The available formulas are listed in “Formulas in Milnor TxE
Electronic Timer Washer-extractors” (see the table of contents).
2.1.2.2.
Split water for final rinse
—In some locations the temperature of the incoming cold water
may be too cold to allow the proper activation of softener chemicals. In these locations, turn
switch position 2
off
(press the side nearest the word “OFF” down) to cause both water valves to
open for all sour/softener steps.
2.1.2.3.
Switch positions not used
—Switch positions 3, 4, 5, 6, and 7 are not used. These
positions have no effect on the operation of the machine.
2.1.2.4.
Normal and diagnostic mode selection
—Switch position 8 determines whether the
machine is configured for normal operation or for diagnostics. With this position
on
, the machine
operates normally by running formulas.
When switch position 8 is
off
, the machine is configured for diagnostics. When switch
position 8 is
off
, connecting an optional display to the processor board aids in diagnosing
problems by allowing a qualified technician to manually actuate outputs individually.
— End of BICEUC01 —